Essential knowledge for wire and cable inspection - Smoke density test

2025-04-26 08:46:20
times

I. Inspection Purpose


When a fire breaks out, the smoke produced is very thick and highly toxic, posing a great threat to people's lives and safety. When wires and cables are burning, they also produce smoke. Currently, many projects require low-smoke and halogen-free cables. This test is an important one for evaluating the low smoke performance of cables.


Ii. Scope of Application


It is applicable to the determination of smoke density when cables are burning under specific conditions.


Iii. Inspection Basis


GB/T 19666—2019


GB/T 17651—2021


Iv. Test Equipment and Apparatus


1. Combustion chamber: Combustion chamber size: 3000±30mm cube.


2. Optical measurement device.


3. Standard fire source.


V. Sampling and Sample Preparation


1. Sample: The sample should consist of one or more cables or optical fibers of 1m±0.05m in length that have been carefully straightened. The sample should be treated at 23℃±5℃ for at least 16 hours.


2. Selection of the number of sample pieces: Select in accordance with the requirements stipulated in the standard.


3. Installation position of the sample: The cable, optical cable or cable bundle sample should be placed horizontally close to each other and at the center above the alcohol tray. The distance between the lower surface of the sample and the bottom of the alcohol tray should be 150mm±5mm.


Vi. Test Procedures


Before the test begins, immediately measure the temperature of the combustion chamber at a height of 1.5m to 2.0m from the ground and a minimum of 0.2m from the wall inside the door. The temperature should be within the range of 25℃±5℃.


2. If necessary, a blank test can be conducted before the test to preheat the combustion chamber.


3. Prepare the fire source for the test.


4. Install the sample, start the fan and ignite the alcohol. Close the airtight door of the combustion chamber.


5. If the light transmittance no longer decreases 5 minutes after the fire source is extinguished or when the test duration reaches 40 minutes, it can be considered that the test has ended.


6. Record the minimum light transmittance.


Vii. Evaluation of Test Results


The minimum light transmittance of cables or optical cables when burning should comply with the relevant standard provisions.


2. In disputed situations, similar cables or optical cables should be taken for two more tests, and the results of both tests should meet the requirements of Article 7.


Tags

  • menu

Telephone: 0755-84890888, 0755-89996999

Suggestion, communication, coordination and complaint channels: 13802568348 (same number for wechat)

Company email: bdk01@163.com

Address: No. 58, Cuijing Road, Pingshan District, Shenzhen City


微信图片_20250807093820

Video Account QR code

奔达康公众号

Qr code of the official account

抖音

Tik Tok QR code

微视

Qr code of Weishi Account

Copyright © Shenzhen Bendakang Cable Co., Ltd All rights reserved record number:粤ICP备18103626号 Mainly engaged inHome decoration wires, fire-resistant cables, and power cable manufacturers, Welcome to inquire! Technical Support: 华企立方 disclaimer
#
在线客服

x